TRAFFIC & PARKING CONTROL CO., Inc.        1.800.236.0112
 

UPS Power Modules pdf pages 100
TOP TOC INDEX MORE INFO. SEARCH

UPS Power Modules  
UPS Power Modules from TAPCO
Enlarge
  • Clean, uninterruptible backup power
  • Wide range Automatic Voltage Regulation (AVR) without going
    to batteries
  • Remote communications via RS-232 port or optional SNMP Ethernet interface
  • Six independently programmable control and report relays
  • Temperature-compensated programmable battery charger
  • Event and alarm logging with time/date stamping
  • Wide operating temperature range of -40 to 74°C

FXM POWER MODULES
The Automatic Voltage Regulator (AVR) offers power stability, reliability, and certainty during unpredictable environmental states and creates voltage equilibrium during varied power conditions. Additionally, the Novus FXM series of power modules are designed to instantly switch to emergency backup power during any utility power failures or interruptions.

  • Part Number 1722-FXM 1100
  • Part Number 1722-FXM 2000
Nominal Specifications
Power Module: FXM 1100** FXM 2000***
Nominal Voltage: 120VAC/230VAC 120VAC/230VAC
Nominal Frequency: 60Hz/50Hz 60Hz/50Hz
Input Current*: 15.5A/8.0A 20A/12A
Output Current: 9.4A/4.9A 17A/8.9A
Output Power: 1100W/VA 2000W/VA
Output Power at 74°C: 850W/VA 1500W/VA
Battery String Voltage: 48VDC 48VDC
Mechanical    
Width (in/mm): 15.5/394 15.5/394
Height (in/mm): 5.2/133 5.2/133
Depth (in/mm): 8.75/222 8.75/222
Weight (lb/kg): 35/16 39/18
TOP TOC INDEX MORE INFO. SEARCH
Notes:
* At nominal V in and 10A battery charger
** Output power for the FXM 650, & FXM 1100 is de-rated by 1.25% per every degree Celsius above 55°C
*** Output power for the FXM 2000 is de-rated by 1.0% per every degree Celsius above 50°C
TOP TOC INDEX MORE INFO. SEARCH
General Specifications
Output    
Input Voltage Range (120VAC): 85 to 175VAC without going to batteries
Input Voltage Range (230VAC): 150 to 328VAC without going to batteries
Output Voltage Regulation: ±10% over full input voltage range
Maximum Charge Current: 10A - user adjustable to 3, 6 or 10A
Waveform: Pure sine wave
Typical Efficiency: >98% (normal mode)
Typical Output Voltage THD: <3%
Typical Transfer Time: <5ms
Audible Noise at 1m: 45dBA
TOP TOC INDEX MORE INFO. SEARCH
Order by phone 1.262.814.7000 Toll Free 1.800.236.0112
or Order by Fax 1.262.814.7017 Toll Free 1.800.444.0331
Traffic and Parking Control Co., Inc
800 Wall Street Elm Grove, WI 53122
© 2008 All Right Reserved